| King KSL-500AP | |
| Complete protection for internet computers and advanced servers. Features :
|
|
| MODEL | KSL-500AP | |
| CAPACITY | Capacity | 500VA |
| OUTPUT | Voltage (on battery) |
Simulated sine wave at 100V / 110V / 115V / 120V or 220V / 230V / 240V +/- 5% |
| Frequency (on battery) |
50 or 60 Hz +/-0.5Hz | |
| Voltage Regulation( AVR) | AVR automatically increase output
voltage 15% above input voltage if -9% to -25% of
nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
|
| Transfer Time | 2 / 4 milliseconds, including detection time | |
| INPUT | Voltage | 100V / 110V / 115V / 120V or 220V / 230V / 240V +/- 25% at line input |
| Frequency | 50 or 60 Hz +/- 5% (auto sensing) | |
| PROTECTION & FILTERING |
Spike Protection | 320 Joules, 2ms |
| EMI/RFI Filter | 10dB at o.15MHz, 50 dB at 30MHz | |
| Unit Input | Fuse for overload & short circuit protection | |
| Overload Protection | UPS automatic power off if overload
exceeds 110% of nominal at 60 seconds and 130% at 3 seconds |
|
| 10 Base-T Cable Port | Network (UTP, RJ-45) compatible jacks | |
| Short Circuit | UPS output cut off immediately or input fuse protection | |
| BATTERY | Type | Sealed, maintenance-free lead acid batteries with 3-6 years typical lifetime |
| Typical Recharge Time | 4 hours (to 90% of full capacity) | |
| Back-up Time (a PC with 15" monitor) |
20 - 30 mins | |
| Protection | Automatic self-test, Discharge protection, Replace battery indicator | |
| PHYSICAL | Net Weight Kg(lbs) | 9.0 (19.8) |
| Dimension WxDxH (mm) | 370 x 330 x 45 (14.6" x 13.0" x 1.8") |
|
| INTERFACE | RS232 | Bi-directional communication port |
| ALARM | Battery Back-up | Slow beeping sound (about 0.47 Hz) |
| Battery Low | Rapid beeping sound (about 1.824 Hz) | |
| Overload | Continuously beeping sound | |
| ENVIRONMENT | Ambient Operation | 3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 ¢J |
| Audible Noise | <40dBA (1 meter from surface) |