| ONL 2000S/3750S/6250S (LCD) | |
| Advanced Power Protection for Enterprise Network Features :
|
|
| TOWER MODEL (LED DISPLAY) | ONL-2000S | ONL-3750S | ONL-6250S | ||
| TOWER MODEL (LCD DISPLAY) | None | ONL-3750LCD | ONL-6250LCD | ||
| POWER RATING | P.F.=0.8 | 2KVA/1.6KW | 3.75KVA/3KW | 6.25KVA/5KW | |
| AC INPUT | Voltage | 110V SYSTEM : 82.5~137.5V 220V SYSTEM : 165 ~ 275 V | |||
| Frequency | 50 Hz or 60 Hz +/- 5 Hz | ||||
| Phase | Single phase | ||||
| BATTERY | DC Voltage | 120V | 192V | 192V | |
| Back-Up Time |
Full Load | 12 mins | 12 mins | 5 mins | |
| Half Load | 30 mins | 29 mins | 15 mins | ||
| Type | Sealed lead acid battery, free maintenance | ||||
| Protection | Battery low cut-off without draining any current | ||||
| Recharge Time | About 8 hours to 90% after fully discharged | ||||
| AC OUTPUT | Frequency | 50Hz / 60Hz | |||
| Voltage, phase | 110 /115 / 120 / 220 / 230 / 240 V Single phase | ||||
| Voltage regulation | +/- 1 % | ||||
| Frequency stability | +/- 0.5 % | ||||
| Power factor | 0.8 ~ 1.0 (lagging) | ||||
| Harmonic distortion | < 3 % of T.H.D. at linear load | ||||
| Overload detection | 125% to 150% for 20 seconds, 150% for 10 cycle | ||||
| EFFICIENCY | Whole | > 80 % | > 84 % | > 85 % | |
| > 86 % | > 88 % | > 90 % | |||
| TRANSFER | Power Failure or Recovery | 0 ms | |||
| Overload Disappear | Auto transfer to UPS | ||||
| UPS to Bypass or vice versa | 0 ms | ||||
| NOISE LEVEL | 1m Distance | < 55 DBA | |||
| LCD INDICATOR | Status | Indicate line, bypass, inv, fault, bat capacity, load capacity | |||
| ALARM | Battery discharge | The first warning will beep every 4 seconds to indicate battery in use. The second warning will beep every 1 second to signal battery low condition. | |||
| UPS fault | Continuous beeping sound | ||||
| ENVIRONMENT | Temperature | 0 - 40 deg | |||
| Humidity | 0 % ~ 95 % (Non condensing) | ||||
| INTERFACE | Dry Contact | Sends AC failure and battery low signals, and receives shutdown signal | |||
| RS232 | Detect power failure, Battery low, Schedule UPS on/off, AC power status display | ||||
| Option | Novell, SNMP, Windows NT, Windows 95/98 | ||||
| PHYSICAL SIZE | W x D x H (mm) | 265 x 532 x 583 10.4"x20.9"x22.9" |
265 x 641 x 750 10.4" x 25.2" x 30.4" |
||
| WEIGHT | Net Weight (Kgs) | 76 (167.2 lb) | 117 (257.4 lb) | 90 (198 lb) | |
BACK