Chinese Website
   
   
Home > Product > Interactive UPS > Smart King AL Series

Smart King AL Series 1000/2000/3000
 

UPS with continuous rated capacity for continous backup main unit excludes internal batteries.

Features :

  • True sinewave output
  • Backup time depends on quantities of connected ext. battery packs
  • Built in fast charger (nominal : 5.5A, 3.5A~8A adjustable)
  • Line interactive design
  • Boost and buck AVR
  • Hot swappable battery by users
  • Fully digitized microprocessor controlled
  • Smart RS-232 communication port
  • Lightning and surge protection
  • Short circuit and overload protection
  • 50/60Hz frequency auto sensing
  • Tel/modem internet spike protection
  • Smart power management with software
  • Cold start (DC power on)
  • Overload, on-line, battery status LED or LCD display
  • Load/Battery power meter display
  • Advanced battery management (ABM)
  • Energy saving (UPS sleep mode)
  • Site wiring fault warning *
  • SNMP capability

    * Feature only for 100V/110V/115V models

Extended Run-time Model
(Battery Excluded)
SAL-1000A SAL-2000A SAL-3000A
INPUT Capacity 1000VA 2000VA 3000VA
Voltage +/-25% at line input, single phase
Frequency 50 or 60Hz +/-5Hz (auto sensing)
OUTPUT Voltage
(on battery)
Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning
Frequency
(on battery)
50 or 60Hz +/-0.5%
Voltage Regulation(AVR) AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal.
AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal
PROTECTION
& FILTERING
Spike Protection 320 Joules, 2ms
Unit Input Fuse for 110V models Except 3000A, breaker for 220V models Except 1000A
EMI/RFI filter 10dB at 0.15MHz, 50 dB at 30MHz
Overload Protection UPS automatic shutdown if overload exceeds 110% of nominal at 20 seconds and 125% at 5 seconds.
Transfer Time 2/4 milliseconds (typical), including detection time
Short Circuit UPS output cut off immediately or input fuse(or breaker) protection
BATTERY Type Hot swappable, sealed, maintenance-free lead acid, with 3-6 years lifetime
Typical Recharge Time 4 hours (to 90% of full capacity)
Protection Automatic self-test & discharge protection, Replace battery indicator
Back up Time
(one PC and one 15" monitor)
¡Ü 90 min ¡Ü 120 min ¡Ü 140 min
Net Weight Kg
(lbs)
Tower 25.0 (55.0 lb) 30.0 (66.0 lb) 30.0 (66.0 lb)
19" Rack-mount 26.1 (57.4 lb) 28.4 (62.5 lb) 28.4 (62.5 lb)
DIMENSION
W x D x H (mm)
Tower 170 x 450 x 226 (6.7" x 17.7" x 8.9")
19" Rack-mount 483 x 381 x 130 (19.0" x 15.0" x 5.1")
LCD Indicators Status Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault statuts, load
INTERFACE RS232 Detect battery low, Schedule UPS on/off, AC input/output power status display.
Dry contact Sends AC fail and battery low signals, and receives shutdown signal from computer.
Option Novell, SNMP, Windows NT, Windows 95/98/2000/ME
ALARM Battery Back-up Slow beeping sound (about 0.25Hz)
Battery Low Rapid beeping sound (about 1.00Hz)
Overload Continuously beeping sound
ENVIRONMENT Ambient Operation 3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 deg
Audible Noise <45dBA (1 meter from surface)
Storage Condition 15,000 meter max. elevation


BACK