| SOLAR KING 1500 / 2000 / 3000 / 4000 / 6000 | |
| The most advanced grid-tie PV inverter in the world. Converting sun light into electricity energy for home / industrial applications, and powering up our world with free solar energy is now no longer just a dream. Features :
|
|
| Model | SLK-1500 | SLK-2000 | SLK-3000 | SLK-4000 | SLK-6000 |
| Input Data | |||||
| Maximum Input Power | 1750W | 2340W | 3510W | 4700W | 6500W |
| Nominal DC voltage | 360V~400V | ||||
| Max. input voltage Maximum PV open voltage |
500VDC | 600VDC | |||
| MPPT voltage range | 150V to 500V +/-5% |
150V to 600V +/-5% | |||
| System start-up voltage | 100 +/-5% | ||||
| Working voltage range * | 100 +/-5% ~ 500-5%+0%V | 100 +/-5% ~ 600-5%+0%V | |||
| Initial feeding voltage * | 150V +/-5% | ||||
| Full rating working range | 200V to 500V | 250V to 500V | 250V to 600V | ||
| Max. input current | 7.5ADC | 10ADC | 15.2ADC | 20ADC | 30ADC |
| Shutdown voltage | 80V typical | ||||
| DC voltage ripple | < 10% | ||||
| DC insulation resistance ** | > 8M ohm | ||||
| DC Switch | On/Off 20A | On/Off 30A | |||
| DC Connector | Tyco or MC contract (1-pair) - cable type | Tyco or MC contact (3 pairs) | |||
| Attachd DC Connector | Tyco-contact (1 pair) | ||||
| Output data | |||||
| Nominal output power | 1500W | 2000W | 3000W | 4000W | 6000W |
| Maximum output power (The time is limited to 10 minutes @ 50°C ambient) |
1650W | 2200W | 3300W | 4400W | 6000W |
| Operational Voltage range *** | 198V, minimum 256V maximum |
||||
| Operational Normal voltage | 230 Vac | ||||
| Operational frequency range | 50/60Hz, auto
selection |
||||
| Nominal output current | 6.6A | 8.7A | 13.1A | 17.4A | 26.1A |
| O/P current distortion | THD<5%, each harmonics <3% | ||||
| Power Factor | > 0.99% | ||||
| DC current injection | <0.5% of rated inverter output current | ||||
| General Data | |||||
| Internal power consumption | < 7W | ||||
| Standby power (at night) | < 0.1W | ||||
| Minimum conversion efficiency (DC/AC) | >90% Under input voltage>210V, load >20% |
||||
| Maximum Conversion Efficiency (DC/AC) | >94% | >95% | >95% | >96% | |
| European Efficiency | >93% | >94% | >94% | >95% | |
| GFCI threshold | See ground fault current detection | ||||
Ground current detection range |
0~500mA | ||||
| Ground current detection frequency | 0~700Hz | ||||
| DC input impedance requirement | >2M Omega | ||||
| Protection degree | IP 65 or IP43 | ||||
| Operation temperature | -25 to 55°C | ||||
| Humidity | 0 to 95%, non-condensing | ||||
| Heat Dissipation | Convection | ||||
| Acoustic noise level | <40dB, A-weighted, frequency up to 20kHz | ||||
| Altitude | Up to 3000m without power derating, 5°C derated for each additional 500m | ||||
* Load curve :

The relation of input DC voltage and output power is shown
in figure. Once input V is less than 250V, the relation
of I/P V and load % is : Load% =
0.4 x Vi
1. This is voltage range that inverter will start to feed
power to grid.
2. The DC resistance requirement for positive or negative
terminal to chasis ground
3. In VDE0126-1-1, it is ¡V20%/ +15%. DK5940, RD1663 are
also available.
4. Based on the limit of VDE0126-1-1
5. Based on limit of IEEE929
6. Under the output voltage is 230VAC
7. Under utility voltage THD<3%
8. under input voltage>= 400V, full rated output power,
25oC ambient
9. According to VDE0126-1-1 requirement
Mechanical Requirements:
| Model | SLK-1500 | SLK-2000 | SLK-3000 | SLK-4000 | SLK-6000 |
| Physical: W*D*H (mm) | 352*300*133 | 352*300*133 | 352*300*133 | 550*300*133 | 550*420*143 |
| Physical: Weight (kg) |
14 | 14 | 14 | 21 | 24 |
| Shipping: W*D*H (mm) |
460*460*265 | 460*460*265 | 460*460*265 | 660*460*265 | 660*580*265 |
| Shipping: Weight (kg) |
16 | 16 | 16 | 23 | 26 |
** The dimension and weight here could be changed due
to product modification